Our Products

HydroRanger 200 HMI

Siemens

Ultrasonic Level Controller

HydroRanger 200 HMI is an ultrasonic level controller for up to six pumps and provides control, differential control, and open channel flow monitoring. For water authorities, municipal water, and wastewater plants, HydroRanger 200 HMI is an economical, low-maintenance solution delivering control efficiency and productivity needed to meet today’s exacting standards.

HydroRanger 200 HMI offers single point monitoring with all models, and optional dual-point monitoring with 6 relay model. In addition, it has digital communications with built-in Modbus RTU via RS 485. The standard 6 relay HydroRanger 200 HMI will monitor open channel flow and features advanced relay alarming and pump control functions as well as volume conversion.

 

It is compatible with SIMATIC PDM, allowing for PC configuration and set-up. Sonic Intelligence advanced echo-processing software provides increased reading reliability. HydroRanger 200 HMI uses proven continuous ultrasonic echo ranging technology to monitor water and wastewater of any consistency up to 15 m (50 ft) in depth. Achievable resolution is 0.1 % with accuracy to 0.25 % of range. Unlike contacting devices, HydroRanger 200 HMI is immune to problems caused by suspended solids, harsh corrosives, grease or silt in the effluent, reducing downtime.

Additional Info

Detail

Range
0,3 … 15 m (1 … 50 ft)
Compatible transducers
ST-H and EchoMax series XPS-10, XPS-15/15F, and XRS-5
Relays
6 relays: rating 5 A at 250 V AC, non-inductive
mA output
0 … 20 mA or 4 … 20 mA